Systems
Wire size calculator
A conductor is sized by the worse of two things: the current it carries and the voltage it loses on the way. Almost every calculator answers the first and drops the second, which is fine until the run gets long. This one does both, tells you which is deciding, and prints the distance at which the answer changes.
Written and edited by Pablo Ruiz Quintero
Last reviewed 2026-09-21 · Nothing you type leaves your browser
The load, and how far it is
Two things decide a wire size and almost every calculator shows you one of them. The current says what the conductor can carry; the distance says how much voltage survives the trip. The bigger of the two answers wins, and which one wins changes with the run.
The textbook continuous load, and the one people get wrong most often. Forty amps at 125 per cent is 50, so it needs a 50 amp breaker — and the charger must be set to 40, not to whatever the breaker says.
Off the nameplate. For air conditioning use the minimum circuit ampacity, not the tonnage.
Panel to load, along the route the cable actually takes. The formula counts the return trip for you.
Ranges, dryers, water heaters, air conditioning, car chargers, subpanels. Twice the voltage means half the current and a quarter of the voltage drop, which is why 240 volt circuits reach so much further on the same wire.
A continuous load is sized at 125 per cent. Car chargers, water heaters and lighting are; a range and a dryer are not.
The conditions
Copper. What almost every branch circuit in a house is made of.
110.14(C). Below 100 amps the 60 °C column is the default; most modern panels are marked 75, and the label inside the door says which.
The table's own baseline. Indoors, a basement, a normal wall.
The table's baseline, and what a normal cable contains.
What the code's informational note recommends for the circuit itself. It is a recommendation and not a rule, which is why a run that exceeds it is legal and still a bad idea.
50 A circuit, copper
6 AWG
10 AWG ground · 1.0% drop · 237.6 V at the load
Both constraints land on the same size
6 AWG carries it, and at 60 ft the drop is only 1.0 per cent. It stays the right answer out to about 183 ft, and past that the distance starts deciding instead.
What the two constraints each say
Ampacity
6 AWG
40 amps at 125 per cent is 50, on the 60 °C column.
Voltage drop
6 AWG
60 ft at 3 % of 240 V.
How far each size reaches at 40 amps
Before the drop passes 3 % of 240 volts.
Every size against your circuit
Table ampacity is the 60 °C column, which is the one you are allowed to use. Usable is after the temperature and grouping factors, which are applied to the 90 °C column and then capped by that same number.
| Size | Table | Usable | Drop | Reaches | Verdict |
|---|---|---|---|---|---|
| 14 AWG | 15 A | 15 A | 6.3% | 29 ft | too small |
| 12 AWG | 20 A | 20 A | 4.0% | 45 ft | too small |
| 10 AWG | 30 A | 30 A | 2.5% | 73 ft | too small |
| 8 AWG | 40 A | 40 A | 1.6% | 116 ft | too small |
| 6 AWG · yours | 55 A | 55 A | 1.0% | 183 ft | ok |
| 4 AWG | 70 A | 70 A | 0.6% | 292 ft | ok |
| 3 AWG | 85 A | 85 A | 0.5% | 367 ft | ok |
| 2 AWG | 95 A | 95 A | 0.4% | 464 ft | ok |
| 1 AWG | 110 A | 110 A | 0.3% | 584 ft | ok |
| 1/0 AWG | 125 A | 125 A | 0.2% | 738 ft | ok |
| 2/0 AWG | 145 A | 145 A | 0.2% | 931 ft | ok |
| 3/0 AWG | 165 A | 165 A | 0.1% | 1,175 ft | ok |
| 4/0 AWG | 195 A | 195 A | 0.1% | 1,480 ft | ok |
The “max” verdicts are 240.4(D), the small conductor rule: 14, 12 and 10 AWG copper are capped at 15, 20 and 30 amps of overcurrent protection whatever the ampacity table says. It is why a 12 AWG circuit in a house is always twenty amps and there is no conversation to be had about it. See the panel page if the question behind this is whether the service can take the load at all.
Worth knowing
- A continuous load — anything running three hours or more — is sized at 125 per cent. 40 amps becomes 50 for the purpose of choosing the conductor and the breaker, which is why this answer is a size larger than the current suggests. It is the rule people get wrong most often on car chargers.
- Sized on the 60 °C column, which is the default at 100 amps and below under 110.14(C). Modern breakers and panels are usually marked for 75 °C, and if yours is — look at the label inside the panel door — you may use the 75 column instead, which is often one size smaller of wire. The 90 °C column on the same table may never be used for the final answer whatever the insulation says; it exists to give you something to derate from.
- Ampacity is what decides here, and it will go on deciding out to about 183 ft. Past that the voltage drop takes over and the answer goes up a size. Worth knowing if the route is not settled yet — going round three sides of a building rather than across it is what usually pushes a run over.
- The equipment grounding conductor is sized from the breaker, not from the conductors it runs beside — 10 AWG here, off Table 250.122. It does not grow when you go up a size for voltage drop, because its job is to carry fault current until the breaker opens and that is set by the breaker.
- What this does not do: conduit fill, which is its own table and its own problem, and it does not know what is in the wall. It also assumes a run at a steady temperature — a conductor that passes through a hot attic is derated for the attic even if only ten feet of it are up there.
On this page — 6 sections
- 01Two constraints, and the crossover nobody shows you
- 02The 90 °C column, and why you almost never get to use it
- 03The 125 per cent rule, and the circuit people get wrong
- 04Voltage drop is not a rule, and it still decides the answer
- 05Copper or aluminium, and what the reputation is actually about
- 06What goes wrong
Two constraints, and the crossover nobody shows you
The short version
- A conductor is sized by the worse of two things: the current it has to carry, and the voltage it loses getting there.
- Which one wins depends entirely on the distance. 12 AWG carries 20 amps all day; past about 45 feet it stops being the right answer.
- The 90 °C column may not be used for the final answer, whatever your insulation says. It is the most misread table in the code.
- Continuous loads are sized at 125 per cent — which is why a 40 amp car charger needs a 50 amp circuit.
Almost every wire size calculator on the internet answers one of these two questions and quietly drops the other. Ask one for 20 amps and it says 12 AWG. Ask it for 20 amps at a hundred and forty feet and it still says 12 AWG, because it never asked how far.
The two constraints are genuinely different things.
Ampacity is about heat. Current through resistance makes heat, and the conductor must not cook its own insulation. It comes from Table 310.16 and then gets corrected for how hot the surroundings are and how many conductors are crowded together. It does not care in the slightest how long the run is.
Voltage drop is about arriving. Every foot of wire has resistance, and resistance takes voltage away from the load at the far end. It cares about nothing except length, current and the metal — and it grows in a straight line with distance while the ampacity sits perfectly still.
Which means there is always a crossover: a distance at which the second constraint overtakes the first and the answer changes. That number is the whole point of this page, and the calculator above prints it for your circuit.
National Fire Protection Association, NFPA 70, National Electrical Code — Article 310, Conductors for General Wiring (2023) · checked 2026-09-21
The 90 °C column, and why you almost never get to use it
This is the part that gets people hurt, and it is a reading error rather than a calculation error.
Modern building wire is THHN or THWN-2, insulated to 90 °C. Look up 12 AWG copper in the 90 °C column of Table 310.16 and it says 30 amps. It is right there in the code, printed in the same table as everything else, and it is not the number you may use.
110.14(C) limits a conductor to the temperature rating of whatever it lands on at each end. Breakers, lugs and equipment terminals are listed for 60 °C or 75 °C — almost never 90. The wire could take the heat; the screw it is under could not, and the connection is where the heat concentrates.
So the rule that actually applies is:
- 01Circuits at 100 amps and belowUse the 60 °C column, unless the equipment at both ends is marked for 75 °C — and most modern panels and breakers are. The label inside the panel door tells you.
- 02Circuits above 100 ampsUse the 75 °C column. Equipment at this size is listed for it as a matter of course.
- 03The 90 °C columnOnly ever as the starting point for derating. Apply your temperature and bundling factors to it, then cap the result at the number in your terminal column. It is headroom, not capacity.
| Copper | 60 °C | 75 °C | 90 °C | Breaker cap |
|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | 15 |
| 12 AWG | 20 | 25 | 30 | 20 |
| 10 AWG | 30 | 35 | 40 | 30 |
| 8 AWG | 40 | 50 | 55 | — |
| 6 AWG | 55 | 65 | 75 | — |
| 4 AWG | 70 | 85 | 95 | — |
| 3 AWG | 85 | 100 | 115 | — |
| 2 AWG | 95 | 115 | 130 | — |
National Fire Protection Association, NFPA 70, National Electrical Code — 110.14(C), temperature limitations at terminations (2023) · checked 2026-09-21
The 125 per cent rule, and the circuit people get wrong
A load expected to run for three hours or more is continuous, and a continuous load is sized at 125 per cent of its current — the conductor under 210.19(A)(1) and the breaker under 210.20(A). The reason is heat again: a breaker is calibrated in open air and derates itself inside a warm panel next to other breakers, so it needs headroom above a load that never lets up.
It is not a subtle adjustment. It is the difference between a 40 amp circuit and a 50 amp one, and the load that trips people up is the obvious one.
| Continuous — sized at 125 % | Not continuous — sized at 100 % | |
|---|---|---|
| Typical examples | EV charger, water heater, hot tub, lighting | Range, dryer, dishwasher, receptacles |
| Why | Runs for hours without a break | Cycles, or is used in bursts |
| 40 amps becomes | 50 amps | 40 amps |
| Wire at 60 °C copper | 6 AWG | 8 AWG |
| Where it bites | Car charging, almost always | Rarely |
3 hr
What makes a load continuous
210.19(A)(1) and 210.20(A)
125%
What it is sized at
Conductor and breaker both
80%
The same rule, said backwards
A 50 A circuit carries 40 continuously
20 A
Cap on 12 AWG copper
240.4(D), whatever the table says
Voltage drop is not a rule, and it still decides the answer
Worth being straight about this, because people arrive convinced they are breaking something. The NEC does not require a voltage drop limit on branch circuits. It appears in an informational note suggesting 3 per cent for the branch circuit and 5 per cent from the service to the load. Informational notes are not enforceable. A run that drops 6 per cent passes inspection.
What it costs you is a different question, and it is not nothing.
What a low voltage at the far end actually does
- A motor draws more current as voltage falls, because it still has to deliver the same mechanical work. More current in a smaller wire means more heat, and motors that run hot die early.
- Resistive heat falls with the square of the voltage. Ten per cent down is nineteen per cent less heat out of a water heater element or a baseboard heater.
- LED drivers at the end of long runs flicker or buzz, and it is usually blamed on the fittings.
- Incandescent and halogen lamps visibly dim, which is the oldest symptom and the one people notice first.
- Well pumps and compressors that start under load may not start at all at the bottom of a long run on a hot day.
- Nothing at all happens to a lightly loaded circuit. Voltage drop is proportional to current, so a 15 amp circuit carrying 3 amps drops a fifth of what the table suggests.
And the arithmetic has two levers worth knowing, because both are free at design time.
Doubling the voltage quarters the loss. The same power at 240 volts is half the current, and the allowance is twice as many volts — so a 240 volt circuit reaches four times as far as a 120 volt one for the same percentage. It is why a long run to a shed is worth doing as a 240 volt feeder to a small subpanel rather than as a 120 volt circuit, even when everything in the shed is 120.
And the same fact upside down is why 12 volt systems are brutal. Three per cent of 12 volts is 0.36 of a volt. A 20 amp load twenty feet away wants 4 AWG — for twenty amps, a current a 12 AWG would carry without noticing. That is the entire reason the off-grid and marine world has moved to 24 and 48 volt battery banks.
National Fire Protection Association, NFPA 70, National Electrical Code — Chapter 9, Table 8, conductor properties (2023) · checked 2026-09-21
Copper or aluminium, and what the reputation is actually about
Aluminium has a bad name in American houses and the reason is specific rather than general — which matters, because the version with the bad history is not the version being sold for feeders today.
In the sixties and seventies, small aluminium branch circuit wire — 12 and 10 AWG, going to ordinary outlets and switches — was installed in millions of homes. The alloy crept under the terminal screw, the connection loosened, the loose connection heated, and houses burned. That wiring is a genuine hazard and a known one, and it is on the list of things a home inspector flags.
Modern AA-8000 series aluminium in the larger sizes is a different thing, and it is not exotic: it is what the utility uses to reach your meter, it is what most 200 amp service entrance cables are, and 4/0 aluminium is the standard residential service conductor across the country. For a subpanel feeder or a service it is ordinary practice, and the saving is large.
| Copper | Aluminium | |
|---|---|---|
| Size for the same current | The baseline | About two sizes larger |
| Cost of the conductor | The expensive half of a long run | Roughly a third |
| Where it belongs | Branch circuits, anything under 60 amps | Services and subpanel feeders |
| Where it does not | — | Small branch circuits, which is the history |
| Terminations | Nothing special | Lugs listed AL/CU, and antioxidant compound |
| On a long run | The drop is lower per size | Cheap enough to just go up a size |
What goes wrong
01Sizing for the current and ignoring the distance
Ampacity does not change with length and voltage drop does nothing but. A 12 AWG that is correct at forty feet is the wrong answer at a hundred and forty, and every table that stops at ampacity will tell you it is fine.
Instead — Take the larger of the two answers, and find out where the crossover is — the calculator above prints it, so you know whether a change of route matters.
02Reading the 90 °C column because the wire says 90 °C
110.14(C) caps the conductor at the terminal rating, which is 60 or 75 °C. The 90 °C column is a starting point for derating and never a final answer. This is how terminations overheat.
Instead — Use the 60 °C column at 100 amps and below unless both ends are marked 75 °C, and check the label inside your panel door before assuming they are.
03Forgetting the 125 per cent on a continuous load
A car charger, a water heater or a run of lighting works for hours without a break, and a breaker in a warm panel needs headroom above that. Forty amps of charging needs a fifty amp circuit.
Instead — Ask whether it runs three hours or more. If it does, multiply by 1.25 before you size anything — and set the appliance to 80 per cent of the breaker afterwards.
04Setting an EV charger to the breaker rating
The breaker is 50 because the load is 40. Setting the charger to 50 puts a continuous 50 amps on a circuit designed for 40 and defeats the whole rule.
Instead — Set the charger to 40, or to 80 per cent of whatever breaker is fitted. It is a commissioning setting and it is routinely left at the default.
05Never derating for the attic
An unvented attic under a dark roof reaches 110 or 120 °F on a summer afternoon, which takes ampacity to 87 per cent or less. The correction applies to the whole run, not to the hot part of it.
Instead — Apply the ambient band honestly, or route the cable below the insulation where the temperature is the room's rather than the roof's.
06Bundling circuits in a conduit without adjusting
Four to six current-carrying conductors in one raceway take every one of them to 80 per cent. Two 20 amp circuits sharing a pipe is already four.
Instead — Count the current-carrying conductors — the neutral of a shared circuit usually counts, the ground never does — and apply the factor, or run a second pipe.
07Sizing an air conditioner circuit from the tonnage
Tonnage is cooling output and tells you nothing about current. The nameplate gives a minimum circuit ampacity and a maximum overcurrent device, and the second one is a ceiling you may not exceed even if a bigger breaker would be convenient.
Instead — Size the conductor to the minimum circuit ampacity and the breaker to no more than the maximum on the plate.
08Upsizing the ground along with the conductors
Not wrong, just unnecessary and expensive. The equipment grounding conductor is sized from the breaker in Table 250.122, and going up two sizes for voltage drop does not change what the breaker is.
Instead — Size the ground off the overcurrent device. The one real exception is when the phase conductors are upsized for voltage drop on a feeder, where 250.122(B) asks for a proportional increase — worth checking on a long feeder.
- 01Find the current, not the wattsOff the nameplate. For air conditioning and heat pumps use the minimum circuit ampacity printed on the plate, which is already worked out for you, and never the tonnage.
- 02Decide whether it is continuousThree hours or more of running means the conductor and the breaker are sized at 125 per cent. Car chargers, water heaters and lighting are continuous; ranges and dryers are not.
- 03Measure the route, not the distanceThe cable goes along joists and around corners, not through the middle of the house. Pace the route it will actually take, one way — the formula counts the return trip itself.
- 04Size it for the currentTable 310.16 in the column your terminals are rated for, then apply the temperature and bundling factors if either applies.
- 05Size it again for the distanceAnd take the bigger of the two answers. This is the step most calculators leave out, and it is the one that matters on any run over about fifty feet.
- 06Check the small conductor rule14, 12 and 10 AWG copper are capped at 15, 20 and 30 amps of protection no matter what the ampacity column says.
- 07Size the ground from the breakerTable 250.122, off the overcurrent device rating. It does not change when you upsize the conductors for distance.
Sizing the wire is the second question. The first is whether the service has the capacity at all, and that is a calculation too — the NEC load method, run on your house, with the panel and the service upgrade priced apart.
If the real question is whether the panel can take it- AWG
- American Wire Gauge. The numbers run backwards — smaller number, thicker wire — and each three steps down roughly doubles the cross-section. Above 1 AWG the sizes continue as 1/0, 2/0, 3/0 and 4/0, spoken as one-aught and so on.
- Ampacity
- The current a conductor can carry continuously without its insulation exceeding its temperature rating. It comes from Table 310.16 and is then corrected for how hot the surroundings are and how many conductors share the raceway.
- Voltage drop
- The voltage lost to the resistance of the wire on the way to the load. It is not a code requirement in the NEC — it lives in an informational note that recommends 3 per cent for a branch circuit — which is why a run can exceed it and still pass inspection.
- Terminal temperature rating
- The temperature the lugs and breaker terminals are listed for, 60 °C or 75 °C. Under 110.14(C) it caps the ampacity you may claim, which is why 90 °C insulation almost never buys you a smaller wire.
- Continuous load
- One expected to run for three hours or more. The conductor and the breaker are sized at 125 per cent of it, which is why a 40 amp car charger needs a 50 amp circuit.
- Derating
- Reducing the table ampacity for ambient temperature or for bundling more than three current-carrying conductors together. It is applied to the 90 °C column, then the result is capped at the terminal rating.
- Small conductor rule
- 240.4(D). Whatever the ampacity table says, overcurrent protection on 14, 12 and 10 AWG copper may not exceed 15, 20 and 30 amps. It is why a 12 AWG house circuit is always twenty amps.
- Equipment grounding conductor
- The protective conductor that carries fault current back so the breaker trips. Sized from the breaker rating in Table 250.122, not from the conductors it runs beside — so it does not grow when you upsize for voltage drop.
- Minimum circuit ampacity
- The figure printed on an air conditioner or heat pump nameplate. It is what the circuit is sized to, already worked out by the manufacturer, and it is not the same as the running current or the tonnage.
- THHN / THWN-2
- The common building wire insulation, rated 90 °C dry and wet. The 90 °C matters for derating headroom and almost never for the final answer, because the terminals it lands on are not rated that high.
- NM-B
- Non-metallic sheathed cable, what most people call Romex. Its conductors are 90 °C but 334.80 requires it to be used at the 60 °C column, so an NM-B run gets the conservative answer whether or not the panel is marked 75.
- Aught
- How the sizes above 1 AWG are spoken: 1/0 is one-aught, 4/0 is four-aught. Four-aught aluminium is the usual 200 amp residential service conductor.
Common questions
- What size wire do I need for a 20 amp circuit?
- 12 AWG copper, and that answer holds to about 45 feet at a full 20 amps on a 120 volt circuit. Past that the voltage drop passes 3 per cent and 10 AWG is the honest answer even though 12 carries the current perfectly well. The ampacity table gives 20 amps for 12 AWG copper at 60 °C, and 240.4(D) caps its breaker at 20 regardless — which is why a 12 AWG circuit in a house is always twenty amps.
- What size wire for a 30 amp, 40 amp or 50 amp circuit?
- On the 60 °C column: 10 AWG copper for 30 amps, 8 for 40, and 6 for 50. If your panel and breakers are marked for 75 °C — most modern ones are, and the label inside the door says — then 8 AWG copper is rated 50 amps and can serve a 50 amp circuit. That is a real and frequently argued point, and it is legal when both ends are marked. Distance can still push any of these up a size.
- What size wire for an electric water heater?
- 10 AWG copper. A 4,500 watt element at 240 volts draws 18.75 amps, and because a tank reheating runs past three hours it is a continuous load sized at 125 per cent — 23.4 amps. That is more than 12 AWG may be protected at, so it lands on 10. The calculation asks for a 25 amp breaker; what is actually fitted everywhere is a 30, and that is correct because 10 AWG carries it.
- What size wire for a level 2 EV charger?
- For a 40 amp charger, 6 AWG copper on a 50 amp breaker if you assume 60 °C terminals, or 8 AWG if your equipment is marked 75 °C at both ends. Charging is the textbook continuous load, so 40 amps is sized as 50 — and the charger itself has to be set to 40, not to whatever the breaker says. Garages also tend to be hot, which is a derating nobody applies.
- Does voltage drop matter, or is it just a recommendation?
- It is a recommendation — an informational note suggesting 3 per cent on a branch circuit and 5 per cent overall — so a run that exceeds it still passes inspection. What it costs you is real all the same: a motor draws more current as voltage falls and heats up doing it, resistive heat output falls with the square of the voltage, and LED drivers at the end of a long run flicker. On a short run it is irrelevant. On a long one it is the whole answer.
- Why does my 12 volt circuit need such enormous wire?
- Because the percentage is calculated against twelve volts. Three per cent of 120 volts is 3.6 volts of headroom; three per cent of 12 volts is 0.36. Same current, same wire, a tenth of the allowance — so a 20 amp run of 20 feet at 12 volts wants 4 AWG where at 120 volts it would want 12. It is exactly why battery systems keep moving to 24 and 48 volts: four times the voltage is a sixteenth of the drop on the same conductor.
- Can I use the 90 °C column if I have THHN?
- No, not for the final answer, and this is the single most misread thing in the whole code. 110.14(C) limits a conductor to the temperature rating of the terminals it lands on — 60 °C at 100 amps and below unless the equipment is marked otherwise, 75 °C above. The 90 °C column exists so that you have somewhere to derate from when it is hot or the conduit is crowded. Reading 30 amps off the 90 °C row for 12 AWG and fitting a 30 amp breaker is how conductors overheat at their terminations.
- Is aluminium wire safe, and what size do I need?
- For services and subpanel feeders it is normal, current practice and what most utilities themselves use: 4/0 aluminium is the standard 200 amp residential service conductor. Aluminium runs about two sizes larger than copper for the same current and costs a fraction. What earned it its reputation was small aluminium branch circuit wire in the sixties and seventies, which is a different alloy and a genuine hazard. Modern AA-8000 series feeder conductors need terminals listed for aluminium and an antioxidant compound on the connections.
- How do I size the ground wire?
- From the breaker, in Table 250.122 — not from the conductors it runs with. A 20 amp circuit gets 12 AWG, a 60 amp gets 10, a 100 amp gets 8 and a 200 amp gets 6, in copper. It does not get bigger when you upsize the phase conductors for voltage drop, because its job is to carry fault current until the breaker opens, and that is decided by the breaker.
- What does derating do to my wire size?
- It reduces the ampacity before you compare it to the load. An attic at 110 °F takes it to 87 per cent, and six current-carrying conductors sharing a conduit take it to 80. Both together take an 8 AWG from 55 amps down to about 38. The attic case is the one nobody applies and almost everybody should — and it applies to the whole run even if only ten feet of it are up there.
- How far can I run 12 AWG wire?
- At a full 20 amps on 120 volts, about 45 feet before the drop passes 3 per cent. At 10 amps it doubles to 91. At 240 volts the same 20 amps reaches 91 feet, because the allowance doubles with the voltage while the drop stays the same. That is the general rule worth carrying: halving the current or doubling the voltage doubles how far you can go, and going up one gauge buys about sixty per cent more.
- Does this calculator handle conduit fill?
- No, and that is deliberate — conduit fill is its own set of tables and depends on the insulation type as much as the gauge. What this does cover is the part of conduit that changes the wire size: bundling more than three current-carrying conductors derates all of them, and that is in the calculator above.
Send this to whoever is paying
The link carries your measurements, so whoever opens it sees the same numbers you are looking at — and you can come back to it yourself tomorrow with the delivery note in front of you.
Plain links, no tracking scripts. Nothing here reports back that you shared it.

About the author
Pablo Ruiz Quintero — Editor
Editor of MaterialsEstimator. Decides which documents count as a source, what every default value is, and where the line sits between what the reader parses and what the engines compute.
More about how this site is edited